Self regulating Heating Cable
The low-temperature controlled heating cable (self-regulating heating belt) developed by Ruihua wonderful used in fire protection, petroleum, chemical industry, iron and steel, electric power and so on to keep pipes, tanks warm and prevent frostbite. This cable is suitable for ordinary areas,hazardous areas and corrosive areas, etc..Product type: DWK (BTV、DXW、DKW、ZKWD、DBW、ZDL), relative to BTVR series of RoychemTemperature
Electrical trace-heating for frost prodection
Water lines and process pipework can become a real problem when temperatures drop below freezing. It’s only when the thaw comes that you realise the damage a split or cracked water pipe can cause.
The (XEL) family of self-regulating,parallel circuit heating cables is used for frost protection of metal and plastic pipes and vessels.With the facility to cut on site to the problem of frozen pipework.
It can also be used for low temperature process maintenance up to 30 ℃。Maximum exposure temperature 90℃.
Will not withstand steam cleaning process.
For safe or hazardous area applications.
Description
grade: low temperature series
Structure type: basic type (J), basic anticorrosive type (J2), shielding & explosion-proof type (P), shielding & anticorrosive type (P2), explosion-proof & protective type (PF), explosion-proof & anticorrosive (PF2)
Voltage grade : 12V, 24V, 36V, 110V, 220V, 380V
Nominal power output (w/m at 10℃): 10W/m, 15W/m, 20W/m, 25W/m, 30W/m
Cable structure :
1. Copper-core wire :7×0.32, 7×0.42, 7×0.50, 19×0.32
2. Conductive plastic layer: common PTC, fire-retardant PTC, fluorin-contained PTC
3. Insulation layer: modified polyolefin, fire-retardant polyolefin, fluorin-contained polyolefin, fluorin material
4. Shielding layer: tinned copper braid, covering density: 80%
5. Restrictive coating: modified polyolefin, fire-retardant polyolefin, fluorin-contained polyolefin, fluorin material
SPECIFICATIONS:
1. Standard color: black
2. Temperature range: Max. working temperature 65±5℃ Max. exposure temperature 90℃
Max. bearing temperature: modified polyolefin: 105℃; fire-retardant polyolefin: 105℃; fluorin-contained polyolefin: 180℃; fluorin material: 205℃
3. Minimum installation temperature:-40℃
4. Start-up current ( 10℃ ): ≤0.4A/m
5. Thermal stability: After circulating for 300times from 10℃to 99℃, cable heat is maintained at 90% and above.
6. Minimum bend radius: At 20℃ :12.7mm At -30℃ :35.0mm
7. Insulation resistance: if cable length is 100m and thermostatic water is 75℃ ,testing insulation resistance is 20MΩ at least. As for shielding or explosive-proof & protective type, test for 1 min between shielding layer and conductive wire core in 2,500VDC in 20℃, insulation resistance is 1200MΩ at least.
Nominal power output at 220 Vac on insulated steel pipes:
|
|
Applications:
|
Advantage
1. Equal temperature safe and reliable
2. Save electric energy
3. Rapidly Temperature increase
4. Low cost of installation and operation
5. Easy to install and maintain
6. Convenient for automatic management